3, WDQX intelligent touch net feed (longitudinal) remote control device

product introduction:
WDQX intelligent remote control device (hereinafter referred to as remote control device) is suitable for traction power supply catenary system with rated voltage DC1800V and below and rated current up to 2000A. It can be used as a catenary power access, isolation, load transfer and catenary disconnection detection device to realize the functions of voltage acquisition, voltage protection, isolation operation and operating environment monitoring at both ends of the isolatin

product introduction:

WDQXThe intelligent remote control device (hereinafter referred to as the remote control device) is suitable for traction power supply catenary system with rated voltage DC1800V and below and rated current up to 2000A. It can be used as a catenary power access, isolation, load transfer and catenary disconnection detection device to realize the functions of voltage acquisition, voltage protection, isolation operation and operating environment monitoring at both ends of the isolating switch.

product features:

  1. Real-time data acquisition: the device exchanges data with the system monitoring master station through 4G/5G wireless communication network, and the system can monitor the real-time data information of the remote control device through the real-time data acquisition interface, such as the voltage value, voltage difference, ambient temperature, battery voltage, etc. at both ends of the isolating switch;
  2. remote control device: remote control of remote control device can be realized, and safety check measures are provided;
  3. WIFIOperation: The device supports the connection with PDA terminal through WIFI in situ, and realizes the functions of data reading, information inquiry, parameter setting and simulation control without opening the box.

technical parameters:

Project

Unit

parameters

Rated voltage

V

DC900

DC1800

Rated insulation voltage

V

DC1800

DC3000

Rated insulation level

Between poles, to ground

isolation fracture

Between poles, to ground

isolation fracture

Power frequency withstand voltage

kV

6.9

8.3

9.2

11

Impulse withstand voltage

15

18

20

24

auxiliary circuit power frequency withstand voltage

kV

2

Rated operating current

A

≤ 2000

Rated short-time withstand current/0.25s

kA

125

Rated peak withstand current

kA

178

Auxiliary power supply and battery

input power

V

DC1800/DC900

power consumption

W

≤ 20

power outage continuous working time

h

≥ 12

Battery rated output voltage

V

14.4

mechanical life

times

≥ 20000

Operation mode

Electric/Manual

Electric operation closing/opening time

s

≤ 3

Communication Interface

4G/5G/GPRSwireless communication interface, WIFI wireless communication interface

protection level

IP54

Standard Dimensions (W×D×H)

mm

650 × 500 × 1450

Installation Method

Ground installation method/column installation method

Product Details

Products