GKDY mine general power control switch cabinet/GKDC mine general power cabinet
GKDK mine general power switch cabinet and GKY mine general power supply cabinet are widely used in non-gas explosion dangerous mine underground and ground applications power distribution room, to provide stable DC power supply for power supply and distribution equipment. Mine general power switch cabinet and mine general power supply cabinet have passed KA certification of national safety standard center.
GKDY mine general power supply control switch cabinet and GKDC mine general power supply cabinet can be used in metal or non-metal mine underground power distribution room to provide stable DC power supply for power supply and distribution equipment. Both the mine power control cabinet and the mine power cabinet have passed the KA certification of the national safety standard center.
Product Parameters
| AC input voltage (50Hz) | AC380V;AC220V |
| power factor | ≥ 0.9 |
| Nominal voltage of DC system | DC220V;DC110V |
| DC output rated current | 30A |
| Battery capacity | 100A·h |
| Overall efficiency | ≥ 90% |
| noise | ≤ 65dB |
| protection level | IP43 |
| standard dimensions (W×D×H) | 800×600×2000(mm) |
products:
(1) Power supply function: 2 channels of mutual backup AC power supply, 10 channels of DC output power supply, 10 channels of AC output power supply, battery backup DC power supply, etc.
(2) Battery management function: Automatically manage battery charging by setting parameters in advance, including battery charging modes such as constant current, floating charge, and even charge, and configure a battery inspection module to detect the voltage status of the single battery in real time.
(3) Insulation detection function: it can detect the insulation performance of each section of bus and all branch circuits, and the number of detection circuits can be modularized; It has the function of AC string-in detection.
(4) Protection alarm function: AC power supply fault alarm, battery pack fault alarm, bus fault alarm, charging module or communication module fault alarm, etc.
(5) Monitoring of power parameters: The power cabinet is equipped with power meters for monitoring the closing bus voltage, control bus voltage, battery pack current and control bus current.
(6) Communication function: The power cabinet can be connected to the SCADA system in the traction substation through the RS485 communication interface to upload various working status information and monitoring data.
-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer