ST420HF Series Combined Electrical Fire Monitoring Detector

ST420F-T1消防-3
ST420F-T1消防-2
ST420F-T1消防-1
ST420F正
ST420F is an intelligent device integrating low-voltage microcomputer line protector, multi-function meter and residual current electrical fire monitoring detector. It not only has the functions of low-voltage line protection, measurement, management and communication, but also can be used as an electrical fire detector to alarm and protect the residual current to eliminate electrical fire hazards.
ST420F products through the double test, can be widely used in thousands of industrial, commercial

Device Introduction

The ST series electrical fire monitoring equipment and ST series electrical fire monitoring detectors developed by our company are based on relevant national standards.

690Vthe following TT, TN system design, to meet all kinds of electrical fire monitoring system requirements.

STseries electrical fire monitoring equipment communicates with various ST series electrical fire monitoring detectors on site, receives and forwards its data, realizes fault alarm, and records and stores faultsinformation; ST series electrical fire monitoring detectors monitor and manage the residual current and temperature electrical fire hazard parameters of the distribution circuit to prevent the occurrence of electrical fires.industrial enterprises.

device is suitable for the centralized monitoring and management of electrical fire prevention in places where electrical fire can occur, such as large shopping malls, living quarters, industrial and mining enterprises, office buildings, shopping malls and hotels.

Device Model

Name

Device Model

Electrical fire monitoring equipment

ST2000FB

ST2000FB-H

Electrical fire monitoring detector

ST420F-L9

ST520F

ST570LF

ST420F

ST420HF

Device Implementation Standard

GB14287.1Electrical Fire Monitoring System-Part 1: Electrical Fire Monitoring Equipment

GB14287.2Electrical Fire Monitoring System-Part 2: Residual Current Electric Fire Monitoring Detector

GB14287.3"Electrical fire monitoring system-Part 3: Temperature measuring type electrical fire monitoring detector"

GB50016Code for fire protection design of buildingsGb50116automatic fire alarm system

Device Features

The electrical fire monitoring equipment is connected with the electrical fire monitoring detector through RS485 bus to form an electrical fire monitoring system;

Electrical fire monitoring equipment can receive and process the residual current and temperature signals sent by various detectors in real time, and display them on the LCD screen at the same time;

When the residual current, over-temperature alarm and power supply, communication failure, the monitoring equipment can send out sound and light alarm signal, displayed on the screen;

Electrical fire monitoring equipment has the functions of data storage, query and alarm control signal output;

Electric fire monitoring equipment shall be powered by dual power supply, and the main and standby shall be switched automatically; the working status of the main and standby power supplies shall be indicated by LED on the panel;

The electrical fire monitoring equipment has a self-check function. After the monitoring equipment is started, first perform a self-check on the machine, and then enter the main interface;

Electrical fire monitoring equipment provided8relay output, used to control the protected circuit or other equipment;

the residual current protection and temperature protection of the distribution circuit by the electrical fire monitoring detector.

electrical fire monitoring device

workcantype

ST420F-L9

ST520F/ ST520F-T4

ST570LF

ST420F/ ST420F-T1

ST420HF

protection function

Residual current protection

√

√

√

√

√

temperature protection

√

-/√

√

-/√

√

measurement function

residual current

√

√

√

√

√

temperature

√

-/√

√

-/√

√

Alarm Record

Alarm Record

8 times

24 times

16 times

16 times

16 times

Maintenance Management

Modify fixed value time

√

√

√

√

√

input and output functions

Switching value input DI

-

-

& radic; Road 8

& radic; Road 2

& radic; Road 8

relay output DO

& radic;1

& radic; Road 3

& radic; Road 4

& radic; Road 2

& radic; Road 4

Analog Output AO

-

-

1 way/2 way

-

1 way/2 way

Residual current input

& radic; Road 9

& radic;1

& radic;1

& radic;1

& radic;1

Temperature input T

& radic;1

-/& radic;4-way

& radic;1

-/& radic;1

& radic;1

function programmable

√

√

√

√

√

communication function

Modbus-RTU Protocol

& radic;1

& radic;1

& radic;1 Road 1 Road

& radic;2/& radic;1

& radic;1 Road 1 Road

Modbus-TCP Protocol

-

-

-

-

-

detectors

-

-

-

-

-

Other Functions

Motor protection function

-

√

-

-

Line protection function

-

-

-

√

√

WiFi

-

√

√

√

√

Print

-

-

-

-

-

Display

LCD black and white screen

2.8 inch color screen

2.8 inch color screen

2.8 inch color screen

2.8 inch color screen

Installation dimensions

body

76.7 × 112.3 × 57.8

103.0 × 64.5 × 95.9

103 × 64.5 × 122.0

103 × 64.5 × 105.9

103 × 64.5 × 122.0

main body opening size

-

87.5 × 50.0

87.5 × 51.0

87.5 × 50.0

87.5 × 51.0

Note: "& radic;" standard features,"" co-option function,"-" does not have this function.

Product Details

Products

Pre-assembled DC traction solution for surface mining transportation