ST420H Series Microcomputer Line Protection Device
technical parameters
Analog Input Loop
|
transformer rated current In |
1A, 5A, 10A, 25A, 100A, 160A, 400A |
|
Rated voltage Un |
AC380V/400V |
|
frequency F |
50/60Hz |
|
Rated leakage current I △n |
1A, 5A, 30A |
|
current circuit |
2In continuous operation; 10In is allowed to operate for 10s 40In allows running for 1s |
|
voltage circuit |
1.2Uncontinuous operation;1.4UnAllow to run10s |
|
power consumption |
No current, voltage <1VA/phase |
Measurement range and accuracy
|
Name |
|
accuracy |
|
current I |
0.5~1.2 In |
≤±0.5%In |
|
voltage U |
0.1~1.2 Un |
≤±0.5%Un |
|
Active power P Electrical degree EP |
|Cosφ|≥0.707 U/Un=(50~120)% I /In=(50~120)% |
≤ ± 1% |
|
power factor COS |
|Cosφ|≥0.707 |
≤ ± 1% |
|
Leakage current I △ |
0.5~1.2 I△n |
≤±1%I△n |
|
current harmonics |
Ih/In=(5~50)% I /In=(50~120)% |
≤±1%In |
|
voltage harmonics |
Uh/Un=(5~50)% U/Un=(50~120)% |
≤±1%Un |
|
analog output |
4 ~ 20mA |
≤ ± 0.5% |
protection action accuracy
|
Current/voltage fixed value |
≤ ± 3% fixed value |
|
|
Delay time T |
T<4s |
≤ ± 35ms |
|
T≥4s |
≤ ± 1% fixed value |
|
|
return coefficient |
Overprotection |
<0.95% fixed value |
|
underprotection |
>1.05% fixed value |
|
-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer