ST420B3 series microcomputer line protection device
1)Device Overview
ST420B3series microcomputer line protection device is a protection of the main body and display module split device, suitable for rated frequency 50/60Hz, rated voltage below 1kV feeder circuit applications. The device is composed of protection main body, display module, special current transformer, zero sequence current transformer and other parts. The display module of the device is installed on the cabinet panel, and the other parts are installed in the cabinet.
2)Device Model

Note:
1) Standard 1 Modbus-RTU communication, display module with WiFi function;
2)AC660V/690V circuit application shall be specified when ordering;
3) See "2.3 Current Transformers" in this chapter for current transformers ".
3)technical parameters
Analog Input Loop
|
transformer rated current In |
1A, 5A, 10A, 25A, 100A, 160A, 400A |
|
Rated voltage Un |
AC380V/400V |
|
frequency F |
50/60Hz |
|
Rated leakage current I △n |
1A, 5A, 30A |
|
current circuit |
2incontinuous operation; 10In is allowed to operate for 10s; 40InAllow to run for 1s |
|
voltage circuit |
1.2UnContinuous operation; 1.4Un is allowed to operate for 10s |
|
power consumption |
No current, voltage <1VA/phase |
Measurement range and accuracy
|
Name |
|
accuracy |
|
current I |
0.5~1.2 In |
≤±0.5%In |
|
voltage U |
0.1~1.2 Un |
≤±0.5%Un |
|
active power P electrical degree EP |
|Cosφ|≥0.707 U/Un=(50~ 120)% I /In=(50~ 120)% |
≤ ± 1% |
|
power factor COS |
|Cosφ|≥0.707 |
≤ ± 1% |
|
Leakage current I △ |
0.5~1.2 I△n |
≤±1%I△n |
|
current harmonics |
Ih/In=(5~ 50)% I /In=(50~ 120)% |
≤±1%In |
|
voltage harmonics |
Uh/Un=(5~ 50)% U/Un=(50~ 120)% |
≤±1%Un |
|
analog output |
4~ 20mA |
≤ ± 0.5% |
protection action accuracy
|
Current/voltage fixed value |
≤ ± 3% fixed value |
|
|
Delay time T |
T<4S |
≤ ± 35ms |
|
T≥ 4s |
≤ ± 1% fixed value |
|
|
return coefficient |
Overprotection |
<0.95 percentfixed value |
|
underprotection |
>1.05 percentfixed value |
|
Auxiliary power supply
|
power supply voltage (both AC and DC) |
AC 85~264V,DC 90~300V |
|
power consumption (normal/protected) |
≤ 3W / 5W |
|
surge current |
≤ 20A |
|
|
|
switch input (standard 8)
|
Isolation Method |
optical isolation |
|
Power supply mode |
Built-in DC24V |
|
response time |
≤ 50ms |
relay output (standard 4 way)
|
R1, R2, R3 |
AC250V 7A,DC30V 7A |
|
R6 |
AC250V 5A,DC30V 5A |
analog (4 ~ 20mA) transmission output
|
transmission parameters |
three-phase current, three-phase voltage, leakage current, active power |
|
Load resistance |
≤ 750Ω |
communication function
|
Modbus-RTUStatute |
1channel, RS485 interface, terminal access |
work environment
|
working temperature |
-25~ +55 ℃ |
|
storage temperature |
-25~ +70 ℃ |
|
relative humidity |
5~ 95% (no condensation or ice inside) |
|
altitude |
<3000m |
|
IPlevel |
≥ IP20 (Panel ≥ IP40) |
4)Contour Installation
Device Body
dimensions: 76.7mm × 112.3mm × 57.8mm (length and widthhigh).

Display Module ST523C
are: 103.0mm × 64.5mm × 45.9mm (length, width and depth), and the opening dimensions of the panel are: 91.5mm × 54.5mm (length, width).

Installation Method
device is the standard 35mm guide rail installation in the cabinet.

device is to install the buckle to fix the opening of the panel, install the four buckles along the grooves at the four corners of the device, and push them forward tightly, so that the front end is squeezed on the cabinet body, so that the device is installed.

5)Terminal Arrangement

6)Terminal Definition

7)Typical Wiring

-
System and software products
-
Communication equipment set
-
DC integrated equipment
-
Communication switch electrical components
-
DC switchgear components
-
ꄶ Mechanical and Electrical Equipment Control Box
-
Medium-pressure protection device
-
ꄶ Circuit breaker accessories
-
ꄶ Low-voltage protection device
-
ꄶ Electrical fire protection device
-
ꄶ Multifunctional instrument
-
ꄶ Intelligent integrated device
-
Communication device
-
Current transformer